System connections: Delta / Star

Input Voltage: 230 V 1 Phase

Output Voltage: 230 V or 110 V 1 Phase

Ratios: 1:1 or 2:1

Regulation: Better than 3.5%

Power Factor: 0.75 Lead to 0.75 Lag

Di-electric Strength: 3 kV for 60 sec

Insulation Resistance: Better than 1000 Mega Ohms

Coupling Capacitance: 0.1 PF for 80 db

Leakage Current: Less than 20 Micro Amps

Common Mode Attenuation: 80 db / 100 db

Construction Standards: As per IS 2026 Part I & II, IS 11171

Type of Execution: Closed Type

Operating Temperature: 0 – 45 degree Celsius

Type of Cooling: Natural or forced air-cooled; oil-cooled optional